|
|
Before you can install the MGS or C chassis, you must consider and implement certain prerequisites. This chapter includes information on the following preinstallation requirements, with any distinctions between chassis types clearly noted:
To ensure general safety, follow these guidelines:
The successful installation of the MGS and C chassis should not require access to the chassis interior; however, if this becomes necessary, the following warning will appear at the beginning of any related procedures:
Failure to observe this warning and act accordingly may result in the potential for shock hazard or electrocution. Before beginning a procedure that requires access to the chassis interior, we strongly advise that you read through the entire procedure. After you read the procedure, if you have any doubts about your ability to perform any part, contact a customer service representative for information on how to proceed.
Following are some basic guidelines when working near electricity:
In addition, use the following guidelines when working with any equipment that might be connected to a power source and is connected to telephone wiring or other network cabling.
Preventing Electrostatic Discharge Damage
Electrostatic discharge (ESD) damage, which occurs when electronic components are improperly handled, can result in complete or intermittent failures. ESD can impair electronic circuitry and equipment. Typically, the successful installation of the MGS or C chassis should not require handling any components; however, always follow ESD prevention procedures.
Following are the guidelines for preventing ESD damage:
The MGS and C chassis must be properly installed and maintained to preclude unintended shutdowns. The MGS and C chassis are designed to operate in a level, dry, clean, well-ventilated, and air-conditioned environment. Each chassis has an internal fan (two in the MGS chassis) that pulls air through the card cage and across the power supply. If either the intake or exhaust vents are blocked, this air-cooling function will be impaired, causing the chassis to overheat and possible shut down. Excessive heat can damage the power supply and components.
If the ambient temperature of the air drawn into the chassis is already higher than desirable, the air temperature inside the chassis will also be too high. This condition can occur when the wiring closet or rack in which the chassis is mounted is not ventilated properly, when the exhaust of one chassis (or other electronic device) is placed so that it enters the air intake vent of the chassis, or when the chassis is the top unit in an unventilated rack. Take precautions to avoid these conditions.
The MGS and C chassis can be used as tabletop systems in a data processing or lab environment. The MGS chassis can also be rack mounted. The chassis are intended for unattended or computer room use. Table 2-1 lists environmental design requirements for the MGS and C chassis.
Depending upon the temperature and cooling capability of your site, the chassis will require at least a minimum amount of clearance (approximately 2 to 4 inches in an enclosed rack or closet) on all sides to prevent the chassis from taking in the exhaust (heated) air of other equipment.
Table 2-1 : MGS and C Chassis Environmental Specifications
The proper location of the MGS or C chassis and the layout of your equipment rack or wiring closet are essential for successful system operation. Equipment placed too close together or inadequately ventilated can cause system malfunctions and possibly shutdowns. In addition, chassis panels made inaccessible by poor equipment placement can make system maintenance difficult.
Read and conform to the following precautions when planning your site layout and equipment locations to help avoid future equipment failures and reduce the likelihood of environmentally caused shutdowns.
Equipment Racks---MGS Chassis Only
Use the Installation Checklist following to assist you with your installation by allowing you to keep track of what was done, by whom, and when. Make a copy of this checklist and make entries as each procedure is completed. Include a copy of the checklist for each system in your Site Log along with your records for the chassis. (See the section "Site Log" on page 2-7.)
Installation Checklist
for site
__________________________________________________________________
MGS/CGS router name: ________________________________
CPT protocol translator name: _______________________________
Chassis serial number: _________________________________
Figure 2-1 : Installation Checklist
The Site Log provides a historical record of all actions relevant to the MGS or C chassis system. Keep the Site Log near the chassis where anyone who performs tasks has access to it. Site Log entries might include the following:
Following are the tools and equipment required to attach the rack-mount or slide-mount kit to the MGS chassis and to install both the MGS and C chassis:
Network Connection Preparation
When setting up your system, you must consider a number of factors related to the cabling required for your console terminal connections. When using RS-232 connections, be aware of the distance limitations for signaling; electromagnetic interference may also be a factor. For telco (telephone company) connections, there are a variety of modular connectors from which to choose. Each of these cabling considerations is described in the following sections.
RS-232 Connection Prerequisites
A variety of similar signaling schemes use the name RS-232. The following scheme, which is used in all modular and fixed-configuration products, is sufficient to control most modems and hardware flow-control schemes. This scheme provides six signals per line, two of them outputs:
The line drivers are supplied with bipolar 12 volt (V) power; an open output signal will be near +12 or --12V. The Receive Data input has a 10,000-ohm resistor to the --12V supply that helps prevent open lines from ringing and causing spurious input to the router. An open Receive Data line will be near --7V, but can vary from --6 to --10V, depending on temperature and component variation.
The length of your networks and the distance between connections depends on the type of signal, the signal speed, and the transmission media (the type of cable used to transmit the signals). For example, standard coaxial cable has a greater channel capacity than twisted-pair cabling. The distance and rate limits in these descriptions are the IEEE recommended maximum speeds and distances for signaling. You can usually get good results at speeds and distances far greater than these; however, the greater-than-maximum distances are not recommended.
For instance, the recommended maximum rate for V.35 is 2 megabits per second (Mbps), but is commonly used at 4 Mbps without any problems. If you understand the electrical problems that might arise and can compensate for them, you should get good results with rates and distances greater than those shown here; however, do so at your own risk.
The following distance limits are provided as guidelines for planning your network connections before installation.
The maximum distance for Ethernet network segments and connections depends on the type of transmission cable used. The unshielded twisted-pair (UTP) cabling used with 10BaseT is suitable for voice transmission, but may incur problems at 10-Mbps data rates. UTP cabling does not require the fixed spacing between connections that is necessary with the coax-type connections. Table 2-2 lists the IEEE recommendations for the maximum distances between 10BaseT station (connection) and hub.
Table 2-2 : Ethernet UTP Maximum Transmission Distances
As with all signaling systems, serial signals can travel a limited distance at any given rate. Generally, the slower the baud rate, the greater the distance. Table 2-3 shows the standard relationship between baud rate and distance for RS-232 signals.
Table 2-3 : IEEE Standard RS-232 Transmission Speed Versus Distance
Balanced drivers allow RS-449 signals to travel greater distances than RS-232. Table 2-4 shows the standard relationship between baud rate and distance for RS-449 signals.
Table 2-4 : IEEE Standard RS-449 Transmission Speed Versus Distance
The distance limits for RS-449 (listed in Table 2-4), which are also valid for V.35 and X.21, are recommended maximum distances. You can get good results at distances and rates far greater than these. In common practice, RS-449 supports 2-Mbps rates, and V.35 supports 4 Mbps without any problems; however, exceeding these maximum distances is not recommended.
When wires are run for any significant distance in an electromagnetic field, interference can occur between the field and the signals on the wires. This fact has two implications for the construction of terminal plant wiring:
If you use unshielded twisted-pair (UTP) cables in your plant wiring with a good distribution of grounding conductors, the plant wiring is unlikely to emit RFI. When exceeding the distances listed in Table 2-2, use a high-quality twisted-pair cable with one ground conductor for each data signal.
If wires exceed the distances in Table 2-2, or if wires pass between buildings, give special consideration to the effect of a lightning strike in your vicinity. The electromagnetic pulse (EMP) caused by lightning or other high-energy phenomena can easily couple enough energy into unshielded conductors to destroy electronic devices. If you have had problems of this sort in the past, you may want to consult experts in electrical surge suppression and shielding.
Most data centers cannot resolve the infrequent but potentially catastrophic problems just described without pulse meters and other special equipment. These problems can cost a great deal of time to identify and resolve; take precautions to avoid these problems by providing a properly grounded and shielded environment, with special attention to issues of electrical surge suppression.
Console and Auxiliary Port Connection Prerequisites
You must adjust the baud rate of your terminal to match the chassis console and auxiliary port default baud rate of 9600 baud, 8 data bits, no parity, and 2 stop bits. Consult your terminal's documentation for this wiring specification. The console port is a data communications equipment (DCE) device, and the auxiliary port is a data terminal equipment (DTE) device. If necessary, refer to Appendix A, "Cabling Specifications," for the console port and auxiliary port wiring scheme required to connect the chassis to a console terminal or to build your own cables.
Network Connection Considerations
Your installation needs will depend on many factors, including the interfaces you plan to use. You may need some of the following data communication equipment to complete your installation:
Table 2-5 lists the components that are included with the shipment of the MGS or C chassis or that are available as options.
Table 2-5 : Descriptions of MGS and C Chassis Components
Copyright 1988-1996 © Cisco Systems Inc.
Description
Minimum
Maximum
Ambient temperature, operating
32°F (0°C)
104°F (40°C)
Ambient temperature, nonoperating
--40°F (--40°C)
185°F (85°C)
Ambient humidity, operating
5% RH1
95% RH
Ambient humidity, nonoperating
5% RH
95% RH
Altitude, operating
--500' (--152 m)
10,000' (3,050 m)
Altitude, nonoperating
--1,000' (--304 m)
30,000' (9,144 m)
Vibration, operating
--
5--500 Hz, 0.5 G, (0.1 oct./min.)
Vibration, nonoperating
--
--
--
5--100 Hz, 1 G, (0.1 oct./min.)
100--500 Hz, 1.5 G, (0.2 oct./min.)
500--1,000 Hz, 1.5 G, (0.2 oct./min.)
1 All values of relative humidity (RH) are noncondensing.
Task
Verified by
Date
Chassis received
Chassis system unpacked
Chassis components verified
Read "Safety Recommendations" section on page 2-1
Installation Checklist copied
Site Log established and background information entered
Site power voltages verified
Site environmental specifications verified
Required tools available
Network connection equipment available
Chassis mounted in rack (optional)
Chassis connected to AC source
Network interface cables and devices connected
ASCII terminal attached to console port
Console port set for 9600 baud, 8 data bits, 2 stop bits, no parity
System boot complete (all Normal LEDs lit)
Transmission Speed
Max. Station-to-Hub Distance
10 Mbps (10BaseT)
328' (100 m)
Baud Rate
Distance (Feet)
Distance (Meters)
2400
200
60
4800
100
30
9600
50
15
19200
25
7.6
38400
12
3.7
56000
8.6
2.6
Baud Rate
Distance (Feet)
Distance (Meters)
2400
4100
1250
4800
2050
625
9600
1025
312
19200
513
156
38400
256
78
56000
102
31
T1
50
15
Component
Description
MGS chassis bus
4-slot Multibus backplane
C chassis bus
2-slot Multibus backplane
Processor cards
CSC/3 or CSC/4
MGS chassis
interface cards
Up to 3 interface cards.
Specific restrictions exist on the number and type of cards that can be used in the chassis.
C chassis
interface cards
1 interface card.
Specific restrictions exist on the number and type of cards that can be used in the chassis.
System memory
32 KB of NVRAM on the CSC-MC memory card.
32 KB of NVRAM and 4 MB of Flash memory on the optional CSC-MC+ Flash memory card.
32 KB of NVRAM and 48 KB of Multibus memory on the optional CSC-MT memory card.1
External connectors
Mounting plates with connectors and appliques for attachment to various types of networks.
Accessories
Rack-mount kit that includes screws and 2 flanges for mounting the MGS chassis in a 19'' rack.
The C chassis cannot be rack mounted.
Options2
Slide-mount kit for the MGS chassis allows chassis interior to be accessed without removing the chassis from an enclosed rack. The C chassis cannot be slide mounted.
Power supplies
MAS-28 110/220 VAC (auto-ranging) power supply.
MAS-27 230 VAC power supply is used in the U.K.
Documentation
(optional)
M and C Chassis Hardware Installation and Maintenance, Router Products (or Protocol Translator) Configuration Guide, Router Products Getting Started Guide, Internetworking Technology Terms and Acronyms, Troubleshooting Internetworking Systems, System Error Messages, Protocol Translator Quick Reference, and Command Summary publications.
1 Because it requires a single card cage slot, the CSC-MT card can be used in the MGS chassis only.
2 The slide-mount kit is available as an option only and is not standard equipment. Documentation to install the slide-mount kit is included with its shipment.
![]()
![]()
![]()
![]()
![]()
![]()
![]()